- Pumps by typeBarrel pumps Vacuum pumpsVertical semi-submersible pumpsScrew pumpsVortex pumpsHermetic pumpsDispersant-emulsifier, homogenizerDosing pumpsImpeller pumpsSewer stationsCantilever pumpsLobe pumpsDiaphragm pumpsMultistage pumpsCast iron monobloc pumpsMotor pumpsMotor diaphragm pumpsEx ATEX pumpPTO driven pumpDouble inlet pumpsInline pumpsGlandless pumpsAxial pumpsPeristaltic pumpsRotary vane pumpsPlunger pumpsSemi-submersible fecal, drainage pumpSubmersible drainage and fecal pumpsSubmersible slurry pumpsPiston pumpsRoller pumps Self-priming centrifgual pumpSanitary, hygienic pumpsBorehole pumpsSolenoid pump dispenserWater supply and fire extinguishing stationsChemical magnetic pumpsCentrifugal pumpsGear pumpsIndustrial hose peristaltic pumps
- Submersible drainage and fecal pumps
- Submersible pump Dreno DNA 65-2/150 T/G with Vortex impeller
Submersible pump Dreno DNA 65-2/150 T/G with Vortex impeller
Also buy with this product
Documentation
Download instructions, catalog for Submersible pump Dreno DNA 65-2/150 T/G with Vortex impeller
Overview

Pump application: DNA series is used for wastewater and wastewater treatment. Its wide channel provides free passage of solid particles, which makes it especially useful in water treatment plants, household, utilities and agriculture. The 4-pole version can be used in applications where continuous maintenance of S1 is required, and is characterized by silent operation.
Characteristics: the main components are made of GG20 cast iron. The double mechanical seal in the back-to-back configuration, located in the oil chamber, guarantees a long service life of the product.
Motor range: short-rotor motor with 2 and 4 poles; thermal protection built into the winding (in models DNA ...- 2/220 and DNA ...- 4/090 thermal protection conductors T1 and T2 must be connected to the control panel); insulation class F 155 ° C; degree of protection of the IP68 engine.
Engine cooling: engine cooling is provided by the liquid in which the pump is immersed.
Limits of use: maximum permissible liquid temperature: 40 ° C with the pump completely submerged; maximum depth of immersion: 20 m; permissible pH value: 6-10; hydraulic characteristics are suitable for liquids with a density of <1.1 kg / dm3; permissible voltage: 220V / 380V ± 5%; permissible frequency: 50 Hz ± 2%.
Symbols:
G-float
M-1 Phase 220V
T-3 phase 380V
M/G-single-phase with float sensor
T/G-three-phase with float sensor
2-4 poles 50 Hz
Horizontal pressure pipe
Characteristics
Producer | Dreno |
Pump capacity, cu.m/hour | 39.6 |
Feed height, m | 12 |
Power capacity, kW | 1,5 |
Output pipe diameter | DN65 |
Rate of turn, rpm | 2 850 |
Protection | IP68 |
Power supply | 3х380 V, 50 Hz |
Explosion protection | No |
Max.flow rate, m3/h | 39.6 |
Max.temperature, C | 40 |
Motor capacitor capacity, µF | 32 |
Max.diameter of solid inclusions, mm | 65 |
Impeller type | vortex impeller |
Seal | Double Mechanical Seal, CA/CE/Viton - SIC/SIC/Viton |
Max. head, m | 12 |
Maximal altitude of immersion under the water surface, m | 20 |
Housing material | Сast iron |
Impeller material | cast iron |
Shaft material | AISI 420 |
Serial number of the pump | DNA |
Country of Origin | Italy |
PumpType | submersible drainage and fecal |
Drive Type | electric |
Installation Type | vertical |
Logistics data: | |
Weight, kg | 30 |
Categories:Submersible drainage and fecal pumpsSewage and sewage pumpsPumps for lowering the flood water levelPumps for SPS (sewage pumping stations)