- Home
- Industrial pumps
- Pumps by manufacturer
- WILOWilo-Drain TSW stainless steel submersible pumpWilo-Drain TMW submersible pump for drainage water drainagePB booster pumpMVI vertical high pressure pumps HELIX FIRST, MVIHorizontal high pressure pumps MEDANA, MHIWell pumps Wilo-Sub TWI 5, TWI 5-SE, TWI 5-SE PNPWILO CronoNorm NL cantilever pumpsWilo-DrainLift KH, TMP Pressure plants for wastewater disposalPumping station Wilo-Jet HWJ with a hydraulic accuHigh pressure glandless pumps MVISSubmersible pumps Wilo-Drain MTS for wastewater diSelf-priming centrifugal pumps Wilo-Jet WJFire extinguishing system Wilo-SiFire ENSpecial IPH pumps for superheated water and thermal oilWilo-FLA-2 pressure boosting systemSewage pumps Wilo EMU FAWILO TOP-S Glandless Circulation PumpsCirculation pumps for heating systems and underflo
- Fire extinguishing system Wilo-SiFire EN
Fire extinguishing system Wilo-SiFire EN

A type
Pressure boosting systems for fire-fighting water supply in accordance with EN 12845.
Contains 1 or 2 pumps, depending on the model, with a horizontal base frame (EN 733), with replaceable clutch, electric or diesel engine and multistage vertical electric feed pump.
Application
Fully automatic water supply for sprinkler-type fire protection systems in residential, office and office buildings, hotels, hospitals, shopping malls and various industrial facilities.
Designation
Example:Wilo-SiFire EN 40 /200-180-7.5 /10.5 /0.55 EDJSiFire
Compact pressure boosting system for fire extinguishing systems.
- EN according to EN 12845.
- 40/200 Main pump type.
- 180 Fact. main pump impeller diameter.
- 7.5 Electric motor power [kW].
- 10.5 Diesel motor power [kW].
- 0.55 Booster pump motor power [kW].
- EDJ Selection.
- E Electric pump.
- E Diesel pump.
- J Jockey pump.
Product Features / Benefits
- Pressure loss-optimized system in accordance with EN 12845 with electrical or diesel driven feed pump to maintain constant pressure in the system.
- Versatile, modular and robust design for safe transport and easy installation.
- Bypass flow to protect the pump with replaceable coupling for easy maintenance.
- High quality SC-Fire control system ready for integration into a building engineering system with busbars BACnet and Modbus.
- Special base frame to minimize vibration, cables are routed inside the structure, which provides maximum reliability and durability.
Performance characteristics
Specifications
- Mains connection 3 ~ 400 V, 50 Hz (1 ~ 230 V, 50 Hz for diesel control panel pump).
- IE2 equivalent standard electric motors, direct injection diesel motor or air or water cooled turbodiesel electric motor.
- Max. ambient temperature: +4 to +40 °C (+10 to +40 °C - if installed diesel pump).
- Max. temperature of the pumped-over liquids: + 40 °C.
- Max. operating pressure: 10 or 16 bar.
- Max. operating pressure 6 bar.
- Volume flow: 10 to 750 m³/h.
- Max. head: 128 m.
- Nominal diameter for connection on the pressure side: DN 65 to DN 250.
- Nominal diameter, inlet side: DN 50 to DN 200.
- Control cabinet protection class: IP54.
- Primary /standby pump with horizontal base frame in accordance with EN 733.
- Epoxy coated piping and hydraulic connections.
- Permitted pumped media:
- non aggressive, clean water;
- fire extinguishing water.